Features
- modernes Industrie Design
- gleiche Abmessungen wie 2 kW und 2,5 kW Geräte
- Schutzklasse IP 55 / UL Type 12 (in Edelstahl IP 56 / UL Type 3, 3R, 4, 4X)
- standardmässig mit Kondensatverdunstung
- Wandanbau oder Halbeinbau
Order Number 851520001 Brand Name SLIMLINE PRO Color RAL 7035 Housing Material Mild steel, powder coated Ingress protection to EN 60 529 Type 3, 3R, 12, 4 Approvals CE, cURus, cULus Accessories Gasket Kit 4Cold air outlet duct 8515/20/25Washable aluminium filter 8515/20/25Vibration Protection Kit 2 Cooling capacity 95F/95F 5120 BTU @ 50 Hz
5120 BTU @ 60 HzCooling capacity 95F/122F 4435 BTU @ 50 Hz
4435 BTU @ 60 HzEER 95F95F 2.1 Compressor type Rotary piston Refrigerant / GWP R 513A / 630 Refrigerant charge 286 g / 10.1 oz High / low pressure 30 / 6 bar
435 / 88 psiAir volume flow (system / unimpeded) Ambient air circuit: 323 / 500 cfm
Cabinet air circuit: 294 / 500 cfmOperating temperature range 50°F - 140°F UL temperature range 50°F - 140°F Mounting Wall mounted / recessed Dimension H x W x D A = Height | B = Width | C = Depth
53.1 x 15.6 x 8.5 inch Weight 97 lbs. Voltage / Frequency 380-415 V 50 Hz 3~
400-460 V 60 Hz 3~UL Voltage / Frequency 460 V / 60Hz 3~ Current 95F95F 1.6 A @ 50 Hz
1.6 A @ 60 HzStarting current 8.2 A Max. current 1.9 A Nominal power 95F95F 700 W @ 50 Hz
880 W @ 60 HzMax. power 1110 W Fuse 15 A (T) Max circuit ampacity 15 A Short-circuit current rating 5 kA Rated current compressor 1.3 A Full load current fans 1.3 A Connection 4 pole terminal block for power
5 pole terminal block for signals
3 pole terminal block for RS 485Datasheet Generate PDF Instruction manual Generate PDF CAD files 2D PDFSTEP Mounting template DWG Certification EC declaration Zertifizierung (UK) UKCA declaration Video SlimLine Pro cleaning and maintenancSLIMLINE PRO Montage Box dimensions 1442 x 495 x 242 mm Gross weight 49 Kg Taric code 84158200