Order Number 4833A4000 Colour RAL 7035 Housing Material ABS Plastic Ingress Protection IP 54 Optional Different housing colours available on request
With NEMA 3R protection part no. 4833A4030Approvals CE, cULus, CSA Operating Temperature Range -10°C - 55°C Air flow unimpeded 670 m³/h - 750 m³/h Static pressure 205 Pa @ 50 Hz
210 Pa @ 60 HzDimensions A x B x C (D+E) A = Height | B = Width | C = Depth
325 x 325 x 160.2 Weight 4.25 kg Cut out dimensions 291 +1.5 x 291 +1.5 Voltage / Frequency 230 V ~ 50/60 Hz Rated current 0.67 A / 0.85 A Power consumption 155 W / 195 W Degree of separation 85% - DIN 24185 Wall thickness 1.5 - 2.5 mm Filter class G3 gemäß EN 779 Installation Elastic clips or by 4 self-threading screws Noise level 66 dB(A) @ 50 Hz