Cooling unit NEMA / type 4X OC 5708-120V

Related Products

Enclosure cooling unit compact line outdoor in stainless steel
Brand Name
SoliTherm NEMA 4X
Order Number
57081162
Housing Material
Stainless steel AISI 304 (V2A)
Ingress protection
IP 56 (TYPE 12, 3, 3R, 4, 4X)
Approvals
CE, cURus, cULus
UL File Nummer
cURus (SA32278)
cULus (E498756)
Optional
With stainless steel AISI 316 (V4A) order no. 57XXXX64
Without cabinet heater order no. 57081062
Taric Code
84158200
Cooling capacity L35L35
750 W @ 60 Hz
Cooling capacity L35L50
470 W @ 60 Hz
Heating capacity
400 W
Compressor
Reciprocating compressor
Refrigerant / GWP
R134a / 1430
Refrigerant charge
235 g / 8 oz
High / low pressure
31.5 / 6 bar
457 / 88 psig
Temperature range
-20°C - +55°C
Air volume flow (system / unimpeded)
Ambient air circuit: 315 / 850 m³/h
Cabinet air circuit: 165 / 170 m³/h
Mounting
External
Dimension HxWxD
830 x 304 x 270 mm
Weight
35 kg
Cut out dimensions
265 x 180
265 x 160 mm
Voltage / Frequency
120 V ~ 60 Hz
Current L35L35
6.4 A
Starting current
22 A
Max. current
7.4 A
Nominal power L35L35
560 W
Max. power
735 W
Fuse
16 A (T)
Connection
Connection terminal block
Datasheet
Generate PDF
Instruction manual
Generate PDF
CAD files
STEP
Mounting template
DXF
Certifications
EC declaration
Video
Service video - ComPact Outdoor cooling units

« back to product overview Cabinet cooling units - UL TYPE 4X

© 2019 Seifert Systems